Seismic Base Shear Calculation Step by Step — ASCE 7-22 Equivalent Lateral Force Worked Example

1:53Published July 8, 2026Narrated, with captions and a full transcriptAlso on YouTube

Calculate the seismic base shear on a two-story light-frame wood building with the ASCE 7-22 equivalent lateral force (ELF) procedure — Chapter 12, start to finish: site class and spectral parameters, Risk Category and Seismic Design Category, R from Table 12.2-1, the approximate period Ta, the seismic response coefficient Cs, base shear V, the story forces Fx, and the diaphragm design forces Fpx.

Transcript and details

About this video

What you will see

  • Adding the Seismic Loads module from the dashboard, and Steps 1 through 8 walked in order
  • Step 1 — each level's seismic weight wx and each story height hsx, one story at a time
  • Step 2 — Table 20.2-1 site classification, then the seven spectral parameters from the ASCE hazard tool: the mapped Ss and S1 (Section 11.4.3), the site-adjusted SMS and SM1 (Section 11.4.3), the design values SDS and SD1 (Section 11.4.4), and the long-period transition TL (Section 11.4.5, Figures 22-14 through 22-17)
  • Step 3 — Risk Category from Table 1.5-1, seismic importance factor Ie from Table 1.5-2, and the Seismic Design Category assigned by entering BOTH Table 11.6-1 (on SDS) and Table 11.6-2 (on SD1) and taking the more severe letter, per Section 11.6
  • Step 4 — Table 12.2-1 reproduced book-style: under A. Bearing Wall Systems, row 16, light-frame (wood) walls sheathed with wood structural panels rated for shear resistance, which sets R = 6.5, the overstrength factor Omega-0 = 3 and Cd = 4, alongside the SDC height-limit columns (no limit in B and C, 65 ft in D, E and F)
  • Step 5 — the approximate fundamental period Ta = Ct x hnx (Eq. 12.8-8), with Ct and x read from Table 12.8-2 and hn taken from the story heights
  • Step 6 — Cs written out with every bound: the Method 2 Eq. 12.8-3, the Eq. 12.8-4 upper bound for T at or below TL, the Eq. 12.8-5 upper bound above TL, the Eq. 12.8-6 floor, and the Eq. 12.8-7 floor that applies when S1 is at least 0.6 g — then V = Cs x W (Eq. 12.8-1), with a plotted design response spectrum showing Ts and the project period
  • Step 7 — vertical distribution: the exponent k, Cvx, story force Fx, story shear Vx and overturning moment Mx (Sections 12.8.3 and 12.8.5), tabulated side by side as E for strength design and 0.7E for allowable stress design
  • Step 8 — diaphragm design forces: the Eq. 12.10-1 column, the minimum column 0.2 x SDS x Ie x Wpx (Eq. 12.10-2), the maximum column 0.4 x SDS x Ie x Wpx (Eq. 12.10-3), and the governing Fpx at each level

The building in this example

Two stories, 40,000 lb of seismic weight and 10 ft of height at each level — W = 80,000 lb, hn = 20 ft. Site Class D, with Ss = 1.0 g, S1 = 0.6 g, TL = 8 s, SMS = 1.0 g, SDS = 0.667 g, SM1 = 0.6 g and SD1 = 0.4 g. Risk Category II, so Ie = 1.0, and both SDC tables return D. Light-frame wood shear walls give R = 6.5, Omega-0 = 3 and Cd = 4. Ta = 0.02 x 200.75 = 0.189 s, well below Ts = 0.60 s, so Eq. 12.8-2 governs: Cs = 0.667/6.5 = 0.1026 and V = 8,209 lb (0.7V = 5,746 lb for allowable stress design). With k = 1 the base shear splits into Fx = 2,736 lb at the lower level and 5,473 lb at the upper level. At the top diaphragm Eq. 12.10-1 governs at Fpx = 5,473 lb; one level down the equation gives only 4,105 lb, so the Eq. 12.10-2 minimum of 0.2 x 0.667 x 1.0 x 40,000 = 5,336 lb takes over — the floor that usually controls ordinary wood diaphragms.

Codes referenced: ASCE 7-22 Sections 11.4, 11.6, 12.8 and 12.10; Tables 1.5-1, 1.5-2, 11.6-1, 11.6-2, 12.2-1, 12.8-2 and 20.2-1; Equations 12.8-1, 12.8-3 through 12.8-8, 12.8-12 through 12.8-14, and 12.10-1 through 12.10-3.

Transcript

The narration word for word, 200 words, from the video's own captions. Select a time to play from there.

Seismic Loads — ASCE 7-22 ELF

0:02In this tutorial we'll find the seismic base shear on a two-story wood building using the Equivalent Lateral Force procedure, per ASCE 7-22 Chapter 12.

Add the Seismic Loads module

0:13From the dashboard, add the Seismic Loads module. It opens empty. Step one, the building: enter each level's seismic weight and story height. Ours is two stories, forty kips and ten feet each — add a story for the second level.

Step 2 — site class & spectral parameters

0:38Step two: pick the site class — D — and enter the spectral parameters from the ASCE hazard tool: the mapped accelerations Ss and S1, the design values, and the long-period transition, TL.

Step 3 — risk category

1:08Step three, the risk category — Category Two, from ASCE Table 1.5-1. Step four, the seismic force-resisting system, straight from Table 12.2-1. Under bearing-wall systems we pick light-frame wood shear walls, which sets R, the overstrength factor, and Cd.

Step 5 — fundamental period

1:27The app then computes the approximate fundamental period in step five. Step six gives the seismic response coefficient Cs and the base shear V. Step seven distributes that base shear up the building into the story forces, Fx.

Step 8 — diaphragm design forces

1:42And step eight gives the diaphragm design forces, Fpx, at each level. That's a complete Equivalent Lateral Force seismic analysis, ready for your report.