How to Calculate Wind Loads on a Building — ASCE 7-22, Step by Step

How to calculate the wind load on a building under ASCE 7-22, following the steps of the code's own Table 27.2-1 — Risk Category and basic wind speed V, the wind load parameters, velocity pressure qz (Eq. 26.10-1), design pressure p on each surface (Eq. 27.3-1) — then the force and base shear, the §27.1.5 minimum design wind load, and W versus 0.6W — worked with real numbers on a gable-roof house, plus which procedure (Chapter 27, 28 or 30) applies and the mistakes that most often get a wind calculation returned.

17 min read Updated November 2, 2026 Written and checked by StructSuite's licensed Professional Engineer (P.E.).
On this page

Wind load is the pressure that moving air puts on a building's surfaces, and the force those pressures add up to. In the United States it is calculated with ASCE 7-22: you find the site's basic wind speed, turn it into a velocity pressure, turn that into a design pressure on every wall and roof surface, multiply each pressure by the area it acts on, and check the result against the code's minimum load.

That is the whole method. The rest of this page does it with real numbers on a two-story gable-roof house, following the steps the code lists in ASCE 7-22 Table 27.2-1 and then carrying the pressures to the base shear and the minimum load, and explains each choice on the way. Every number comes from the calculation engine that runs StructSuite's free Wind Loads module — the same numbers as the full Chapter 27 worked example, where every surface and load case is carried to the end.

The wind load formula chain (ASCE 7-22, Chapter 27)

1. Basic wind speed V for the site and Risk Category — Figure 26.5-1, or the ASCE 7 Hazard Tool

2. Velocity pressure: qz = 0.00256 Kz Kzt Ke V² (psf, V in mph) — Eq. 26.10-1

3. Design pressure on each surface: p = q Kd G Cp − qi Kd (GCpi) — Eq. 27.3-1

4. Force on each surface: F = p × A; windward plus leeward wall forces (and the roof's horizontal component) give the base shear

5. Not less than 16 psf on the wall area and 8 psf on the roof area, projected onto a vertical plane normal to the wind — §27.1.5

What "wind load" means: MWFRS and components and cladding

ASCE 7-22 calculates wind load for two different things, and the first decision is which one you are designing. The definitions in §26.2:

  • Main wind force resisting system (MWFRS): "An assemblage of structural elements assigned to provide support and stability for the overall building or other structure. The system generally receives wind loading from more than one surface." — the shear walls, diaphragms, frames and foundation that hold the whole building up against the wind.
  • Components and cladding (C&C): "Elements of the building envelope or elements of building appurtenances and rooftop structures and equipment that do not qualify as part of the MWFRS." — roof sheathing, siding, windows, doors, and the studs, rafters and fasteners that hold them.

The two start from the same velocity pressure but use different pressure coefficients. C&C pressures are highest at roof edges and corners and depend on the element's effective wind area, so a C&C pressure is normally larger than the MWFRS pressure on the same surface. This page is the MWFRS calculation — the one that gives the base shear for the lateral system.

Which ASCE 7-22 procedure to use

ProcedureChapterUse it forPressure equation
Directional Procedure27The MWFRS of buildings of all heights (regular-shaped, §27.1.2)Eq. 27.3-1
Envelope Procedure28The MWFRS of low-rise buildings: h ≤ 60 ft and h not more than the least horizontal dimension (§26.2), flat, gable or hip roofEq. 28.3-1: p = qh Kd [(GCpf) − (GCpi)]
Components and cladding30Roof and wall elements, cladding and their fastenersChapter 30

Chapter 28's own User Note says that for the buildings it covers, the Envelope Procedure "generally yields the lowest wind pressure of all the analytical methods specified in this standard." Chapter 27 has no height limit, which is why it is the method you can always fall back on and the one this page follows. A house like the one below qualifies for both; whichever you pick, use one procedure for the whole MWFRS calculation. The Chapter 28 worked example runs the Envelope Procedure on a similar house.

The building

A two-story wood-frame house with a gable roof:

InputValue
Plan48 ft along the ridge × 32 ft across it
Eave / ridge height18 ft / 26 ft
Mean roof height h22 ft (average of eave and ridge, §26.2)
Roof slope6:12, θ = 26.57°
Basic wind speed V100 mph
ExposureC
EnclosureEnclosed

Step 1 — Risk Category and basic wind speed V

Table 27.2-1 starts with the Risk Category (Table 1.5-1) — an ordinary house is Risk Category II — because the wind speed map depends on it. §26.5.1 assigns one map per category (Figure 26.5-1A for I through 26.5-1D for IV) and permits, as an alternative, the basic wind speeds "from the ASCE Wind Design Geodatabase", which the ASCE 7 Hazard Tool serves by address. That is how you get the wind speed for a zip code or a street address: enter the site and the Risk Category, read V.

V is a 3-second gust speed at 33 ft above ground in Exposure C (§26.2). This house uses V = 100 mph.

Step 2 — The wind load parameters

With V in hand, Chapter 26 supplies seven more parameters before any pressure can be computed (Table 27.2-1, Step 3; §27.2.1 lists them with V). For this house:

ParameterWhere it comes fromThis house
Wind directionality factor Kd§26.6, Table 26.6-1 (buildings, MWFRS)0.85
Exposure category§26.7 — the terrain upwind of the siteC (open terrain)
Topographic factor Kzt§26.8, Figure 26.8-11.0 (no hill, ridge or escarpment)
Ground elevation factor Ke§26.9, Table 26.9-11.0 (§26.9: "It is permitted to take Ke = 1 for all elevations.")
Gust-effect factor G§26.11.1 — "permitted to be taken as 0.85" for a rigid building0.85
Enclosure classification§26.12Enclosed
Internal pressure coefficient (GCpi)§26.13, Table 26.13-1+0.18 and −0.18

Exposure is the choice that moves the result most, and §26.7 sets it from the ground surface roughness upwind of the site:

  • Exposure B — Surface Roughness B (urban and suburban areas, wooded areas, numerous closely spaced obstructions the size of single-family dwellings or larger) prevails upwind for more than 1,500 ft, for a building with h ≤ 30 ft. Most residential subdivisions.
  • Exposure D — Surface Roughness D (flat, unobstructed areas and water surfaces) prevails upwind for more than 5,000 ft or 20 times the building height, whichever is greater.
  • Exposure C — "shall apply for all cases where Exposure B or D does not apply": open terrain with scattered obstructions generally under 30 ft high, open country, grasslands.

The full Chapter 27 example has excerpts of Table 26.6-1, Table 26.10-1 and Table 26.13-1; the Wind Loads module shows each table in the code's own layout with the selection highlighted.

Step 3 — Velocity pressure qz (Eq. 26.10-1)

qz = 0.00256 · Kz · Kzt · Ke · V² (psf, with V in mph)

Where 0.00256 comes from. It is Bernoulli's dynamic pressure, ½ρV², for standard air with V converted from mph to ft/s — ASCE 7-22 Commentary §C26.10.2 derives it: ½ × 0.002378 × (V × 88/60)² = 0.00256 V² psf, where 0.002378 is the density of standard air in foot-pound-second units and 88/60 converts mph to ft/s. A "wind load calculator" that stops at 0.00256 V² × area has computed only this term; the code then adjusts it for height and terrain (Kz), topography (Kzt), altitude (Ke), and in the next step for direction (Kd), gusts (G) and the shape of the building (Cp).

Kz comes from Table 26.10-1. For Exposure C the table gives 0.90 at 20 ft and 0.94 at 25 ft, so at the mean roof height:

Kh = 0.90 + (22 − 20)/(25 − 20) × (0.94 − 0.90) = 0.916

qh = 0.00256 × 0.916 × 1.0 × 1.0 × 100² = 23.45 psf

qh (qz at z = h) is the value the leeward wall, the sidewalls, the roof and the internal pressure all use. Only the windward wall uses qz at each height z — for this house 21.76 psf from grade to 15 ft (the 0–15 ft row of Table 26.10-1, Kz = 0.85), 22.53 psf at the 18-ft eave, and up to 24.27 psf at the 26-ft ridge on the gable end when the wind blows along the ridge.

Two inputs move everything. Same house, same height, through the same engine:

• Exposure: B → qh = 16.28 psf (Chapter 27; Chapter 28 uses Kh = 0.70 below 30 ft in Exposure B, per the Table 26.10-1 footnote); C → 23.45 psf; D → 28.06 psf.
• Wind speed: V = 110 mph instead of 100 → qh = 28.37 psf. Pressure goes with V², so 10% more speed is 21% more pressure.

Step 4 — Design pressure p on each surface (Eq. 27.3-1)

p = q · Kd · G · Cp − qi · Kd · (GCpi)

q = qz on the windward wall and qh everywhere else; for an enclosed building qi = qh. The first term is the outside air pushing on (positive) or pulling off (negative) the surface; the second is the air inside the building doing the same from the other side.

External pressure coefficients Cp come from Figure 27.3-1. On the walls: +0.8 windward, −0.7 on the sidewalls, and on the leeward wall a value set by the building's depth along the wind, L/B — here −0.5 with the wind across the ridge (L/B = 32/48 = 0.67).

Windward wall at z = h = 22 ft:

p = 23.45 × 0.85 × 0.85 × 0.8 − 23.45 × 0.85 × (±0.18) = +9.97 psf (with +GCpi) or +17.14 psf (with −GCpi)

Leeward wall, wind across the ridge:

p = 23.45 × 0.85 × 0.85 × (−0.5) − 23.45 × 0.85 × (±0.18) = −12.06 psf (+GCpi) or −4.88 psf (−GCpi)

Every surface is computed twice, once for each sign of GCpi, because the inside of the building can be pressurized or under suction and different elements are governed by different signs. The roof gets its own coefficients by slope and h/L (for this 6:12 roof the windward slope has two, −0.33 and +0.15, and both are checked), and the wind is run in both directions — across the ridge and along it. The full Chapter 27 example tabulates every surface for both.

Step 5 — From pressure to force: base shear

A pressure becomes a force when it is multiplied by the area it acts on: F = p × A. For the lateral system the number that matters is the base shear in each direction:

  • the windward wall pushes and the leeward wall pulls, both in the direction of the wind, so their forces add;
  • the internal pressure acts equally on the inside of both walls, so GCpi cancels from the base shear;
  • for a roof slope of 10° or more, the horizontal component of the roof pressures is included (for this house it adds to the shear).

For this house the engine gives, at full design pressure (Load Case 1 of Figure 27.3-8):

Wind directionBase shear, W
Across the ridge (loads the 48-ft face)23,089 lb
Along the ridge (loads the 32-ft gable end)13,751 lb

Chapter 27 does not stop at one direction at full pressure. §27.3.5 requires the four design wind load cases of Figure 27.3-8: full pressure on each axis alone, 75% with a torsional moment, 75% on both axes at once, and 56.3% on both axes with torsion. For this house Case 1 governs the base shear and Cases 3 and 4 govern the roof uplift (21,125 lb). The Chapter 27 example works all four. An exception to §27.3.5 lets buildings that meet Section D.1 of Appendix D be designed for Cases 1 and 3 only — Appendix D exempts, among others, buildings of two stories or fewer framed with light-frame construction, which includes this house; check its conditions before dropping Cases 2 and 4.

Step 6 — Check the minimum design wind load (§27.1.5)

ASCE 7-22 sets a floor under the calculated pressures. §27.1.5 requires the MWFRS wind pressure of an enclosed or partially enclosed building to be not less than 16 psf multiplied by the wall area and 8 psf multiplied by the roof area, both projected onto a vertical plane normal to the assumed wind direction, with the wall and roof loads applied simultaneously.

Wind directionProjected wall areaProjected roof areaMinimumCalculated (Step 5)
Across the ridge48 × 18 = 864 ft²48 × 8 = 384 ft²16 × 864 + 8 × 384 = 16,896 lb23,089 lb
Along the ridge32 × 18 + ½ × 32 × 8 = 704 ft²0 (the roof falls inside the gable-end silhouette)16 × 704 = 11,264 lb13,751 lb

With the wind along the ridge, the triangular gable end is wall, so the whole end silhouette takes 16 psf. Here the calculated loads are larger in both directions, so they govern. The minimum depends only on the silhouette, not on wind speed or exposure: build the same house in Exposure B and the Case 1 base shears drop to 15,783 lb and 9,376 lb, below the minimums, which then govern both directions.

Step 7 — Strength level W, or 0.6W for allowable stress design

ASCE 7-22 wind loads are strength-level (W). The allowable stress design combinations of §2.4.1 use 0.6W (for example combination 5a, D + 0.6W). For this house:

Across the ridgeAlong the ridge
Base shear, W (strength design)23,089 lb13,751 lb
Base shear, 0.6W (allowable stress design)13,853 lb8,251 lb

The wood shear wall guide shows how a base shear like this is distributed to the walls and designed.

Mistakes that get a wind calculation returned

  • Kd counted twice. In ASCE 7-22, Eq. 26.10-1 has no Kd; it appears in the pressure equation (Eq. 27.3-1). Spreadsheets that also put it in qz apply it twice.
  • Exposure read from the site instead of upwind. §26.7 looks at the ground surface roughness upwind of the building. A house on an open lot inside a subdivision is usually Exposure B; a house facing open fields or water may be C or D.
  • Only one GCpi sign. Walls and roofs each need both columns; the larger wall load comes from −GCpi, the larger suction from +GCpi.
  • C&C pressures used for the MWFRS, or the reverse. The shear walls and diaphragms get Chapter 27 or 28 loads; sheathing, studs and fasteners get Chapter 30 pressures for the wind acting on them directly. Some elements need both — Commentary C26.2: "Components can be part of the MWFRS when they act as elements in shear walls or roof diaphragms, but they may also be loaded directly by wind as individual elements."
  • Mixing the two MWFRS procedures. Chapter 27 Cp values and Chapter 28 GCpf zones belong to different methods; one calculation uses one.
  • Skipping the minimum. At low wind speeds, in Exposure B and on long, low buildings, the §27.1.5 floor often governs.
  • Stopping at 0.00256 V² × area. That is the dynamic pressure of the wind, not the design pressure of a building.

Summary of results

QuantityValue
Basic wind speed V (Risk Category II)100 mph
Kh (Exposure C, h = 22 ft)0.916
Velocity pressure qh23.45 psf
Windward wall pressure at h+9.97 / +17.14 psf
Leeward wall pressure (wind across the ridge)−12.06 / −4.88 psf
Base shear W, across / along the ridge23,089 / 13,751 lb
§27.1.5 minimum, across / along the ridge16,896 / 11,264 lb
Base shear 0.6W, across / along the ridge13,853 / 8,251 lb
Governing roof uplift (Cases 3 and 4)21,125 lb

Frequently Asked Questions

What is wind load?

Wind load is the pressure moving air exerts on a building — pushing on the windward wall, pulling on the leeward wall, sidewalls and usually the roof — and the force those pressures add up to. ASCE 7-22 calculates it for the main wind force resisting system (the structure as a whole) and separately for components and cladding (the envelope and its fasteners).

What is the formula for wind load?

Under ASCE 7-22 Chapter 27 it is two equations: the velocity pressure qz = 0.00256 Kz Kzt Ke V² (Eq. 26.10-1, psf with V in mph), then the design pressure p = q Kd G Cp − qi Kd (GCpi) (Eq. 27.3-1) on each surface. The force on a surface is p times its area, and the result is checked against the §27.1.5 minimum of 16 psf on walls and 8 psf on the roof's projected area. Chapter 28 replaces Eq. 27.3-1 with p = qh Kd [(GCpf) − (GCpi)].

How do I find the wind load requirements for my zip code or address?

What varies by location is the basic wind speed V. Read it from the ASCE 7-22 maps (Figure 26.5-1, one map per Risk Category) or, as §26.5.1 permits, from the ASCE Wind Design Geodatabase through the ASCE 7 Hazard Tool: enter the address and the Risk Category and it returns V. Everything else — exposure, topography, the building's shape — is decided for the specific building, so there is no single "wind load for a zip code"; V goes into the steps on this page. Your local building department may also adopt a design wind speed or amendments, so check the jurisdiction's adopted code.

Is wind load the same as wind pressure?

No. Pressure is force per unit area (psf) on one surface; wind load usually means the resulting force (lb) on a surface or on the whole building. For this house the design pressures are about 10 to 17 psf on the windward wall, and the base shear they produce is 23,089 lb across the ridge.

What is a typical wind load on a house in psf?

There is no single value — it depends on wind speed squared, exposure and height. For this two-story house at V = 100 mph in Exposure C, qh is 23.45 psf and the MWFRS wall pressures are roughly +9 to +18 psf windward and −3 to −15 psf on the leeward and side walls. In Exposure B the same house has qh = 16.28 psf (Chapter 27). Individual surface pressures can be lower than 16 psf; what §27.1.5 limits is the total MWFRS load, which is never less than 16 psf × the projected wall area plus 8 psf × the projected roof area.

Does this cover components and cladding?

No. This is the MWFRS calculation. Components and cladding — sheathing, siding, windows, doors, rafters, studs and their fasteners, for the wind acting on them directly — use Chapter 30, which starts from the same qh but uses zone coefficients that depend on the element's effective wind area and are highest at roof edges and corners. StructSuite's wind module computes the MWFRS pressures only.

Should I use the directional or the envelope procedure?

Chapter 27 (Directional) works for buildings of all heights; Chapter 28 (Envelope) is limited to low-rise buildings with flat, gable or hip roofs and, by its own User Note, generally gives the lowest MWFRS pressures for them. For a house that qualifies for both, either is acceptable — use one consistently. See the Chapter 28 worked example for the envelope method on a similar house.

Can I calculate wind loads for free?

Yes. StructSuite's Wind Loads module runs both MWFRS procedures of ASCE 7-22 — Chapter 27 and Chapter 28 — free in the browser, with every equation substituted and the code table behind each value shown. Printing the calculation report is part of the Pro plan.