Dead and Live Loads: Which Value Goes on Which Member (ASCE 7-22)

Where engineers go wrong with ASCE 7-22 Table C3.1-1a and Table 4.3-1: roof dead load per square foot of roof surface against the horizontal projection, a rafter worked both ways, framing weight against the table's complete wood floors, wall and partition weights, the attic rows, and what each StructSuite module expects you to enter.

20 min read Updated November 20, 2026 Written and checked by StructSuite's licensed Professional Engineer (P.E.).
On this page

The two load tables of ASCE 7-22 look simple. Table C3.1-1a lists what materials weigh. Table 4.3-1 lists the live load for each use. The mistakes happen one step later, when a number from a table is put on a member: a roof dead load measured along the slope lands on a span measured on plan, a wall weight is read as a floor load, or the weight of the joists is counted twice.

This page goes through those steps one at a time. Each section says what the table value means, where the usual mistake is, and what to enter in StructSuite's free Dead and Live Loads module and in the member modules that take the load afterwards. One rafter is worked in full, both correct ways and three wrong ways, with the numbers from the calculation engine.

The short answers

Sloped roof, dead load: the table weights are per square foot of roof surface. On the horizontal projection the same roof weighs D ÷ cos θ: 21.25 psf of surface is 23.76 psf of plan at 6 : 12.

Sloped roof, roof live load and snow: already per square foot of horizontal projection. They are not converted.

Convert once. A 2 × 10 rafter on a 17 ft span carries 2,108 lb-ft done right, 2,243 lb-ft with the dead load converted twice, and 1,987 lb-ft with the conversion forgotten.

Walls and partitions: their table weights are per square foot of wall. Multiply by the height for a line load; never read them as a floor load.

What the two tables give you

Table C3.1-1a, Minimum Design Dead Loads, is in the commentary of Chapter 3. Section 3.1.1 defines the dead load:

Dead loads consist of the weight of all materials of construction incorporated into the building including, but not limited to, walls, floors, roofs, ceilings, stairways, built-in partitions, finishes, cladding, and other similarly incorporated architectural and structural items, and the weight of fixed service equipment, including cranes and material handling systems.

Section 3.1.2 adds that the actual weights of the materials are to be used. The table is the commentary's list of those weights, "an extended list that will be useful to designer and official alike". Two things follow, and most of this page comes from them:

  • A table value is the weight of a material per square foot of the surface it covers. A shingle weighs 2 psf of the roof it lies on, whatever the pitch. A stud wall weighs 8 psf of wall.
  • The table is a list of components. The dead load of a roof is the sum of the components that are in it, and nothing puts a component in for you.

Table 4.3-1, Minimum Uniformly Distributed Live Loads, is part of the standard itself. It gives the smallest live load Lo allowed for each occupancy or use, with a concentrated load for some rows and the sections where a reduction is permitted.

Building a dead load, line by line

Framing: the joists alone, or a complete floor

Table C3.1-1a prints joist weights in one place only, a block headed FLOORS, WOOD-JOIST (NO PLASTER) and then DOUBLE WOOD FLOOR, with 2 × 6 to 2 × 12 joists at 12, 16 and 24 in spacing. It is easy to read those twelve values as the weight of the joists. They are not: each is a complete floor, the joists and two layers of board flooring.

The arithmetic shows it. A 2 × 10 is 1.5 in by 9.25 in. At 34 pcf (Table C3.1-2, Douglas fir, coast region) and 16 in spacing, the joists alone weigh

34 × (1.5 × 9.25 ÷ 144) ÷ (16 ÷ 12) = 2.5 psf

and the table gives 6 psf for that row. The difference is about 4 psf in all twelve rows, which is two layers of wood flooring.

JoistsBare joists (psf)Table row (psf)
2 × 6 at 24 in1.05
2 × 8 at 16 in1.96
2 × 10 at 16 in2.56
2 × 12 at 12 in4.08

Two mistakes come from reading the block as bare joists:

  • On a floor: adding a subfloor and a finish floor to a row that already holds a double wood floor. The flooring is counted twice.
  • On a roof or a ceiling: using the row for rafters or ceiling joists. It puts about 4 psf of floor boards where there are none.

In the module the picker therefore opens with its own wood framing lines, 2 × 4 to 2 × 12 at 12, 16 and 24 in, computed from the 34 pcf density and the actual size. Their banner says they are computed and are not rows of the table. The table's twelve rows are still there, named "Double wood floor on 2 × 10 joists, 16 in spacing", for a floor that really is built that way.

Rows priced by thickness

Some rows give a weight per inch or per 1/8 in of thickness, not a finished weight. Gypsum board is 0.55 psf per 1/8 in, so a 1/2 in board is 2.2 psf. Plywood is 0.4 psf per 1/8 in, so 5/8 in is 2.0 psf. The six insulation boards are per inch: polystyrene foam is 0.2 psf per inch, so 4 in of it is 0.8 psf. The picker asks for the thickness on every one of these rows and states it on the line.

Weights the table gives in a header or a note

Two values have no row of their own and are easy to miss:

  • The clay tile block is headed "Clay tile (for mortar add 10 psf)". A mortar-set tile roof is the tile row plus 10 psf. The module has a line "Mortar for clay tile" at the end of that block.
  • The table's note on masonry says the weights include mortar but not plaster, and to add 5 psf for each face plastered. The note prints with any masonry wythe you pick.

The total is only what you listed

A preset or a hand-built assembly weighs exactly its lines. A real floor also carries light fixtures, sprinkler pipe, ducts and wiring, and a roof may get a second covering later. Many engineers add a miscellaneous allowance for this as a line of its own, so the plan checker can see it. The module's presets do not include one. The Typical and Heavy floor and ceiling presets carry a duct allowance and nothing else of this kind. The "Miscellaneous" button adds the line.

Sloped roofs: surface or horizontal projection

This is the one that changes numbers.

Dead load is on the surface

The roof's components are installed on the slope and weighed per square foot of the slope. A roof assembly that totals 21.25 psf weighs 21.25 lb for every square foot of roof surface.

A rafter is nearly always designed on its horizontal span: the span between supports measured on plan. One foot of horizontal run holds more than one foot of roof, because the roof is longer than its plan. For a slope of rise : 12,

slope factor = √(1 + (rise ÷ 12)²) = 1 ÷ cos θ

and the dead load per square foot of plan is the surface value multiplied by that factor.

Roof slopeAngle θSlope factor21.25 psf of surface, on plan
3 : 1214.04°1.03121.90 psf
4 : 1218.43°1.05422.40 psf
5 : 1222.62°1.08323.02 psf
6 : 1226.57°1.11823.76 psf
8 : 1233.69°1.20225.54 psf
10 : 1239.81°1.30227.66 psf
12 : 1245.00°1.41430.05 psf

At 4 : 12 the difference is 5%. At 12 : 12 it is 41%.

Roof live load and snow are on the projection

These are the other way round. ASCE 7-22 defines them on plan. Section 4.8.2, on the roof live load:

where Lr is the reduced roof live load per ft2 (m2) of horizontal projection supported by the member, and Lo is the unreduced design roof live load per ft2 (m2) of horizontal projection supported by the member (see Table 4.3-1).

And Section 7.4, on snow:

Snow loads acting on a sloping surface shall be assumed to act on the horizontal projection of that surface.

So 20 psf of roof live load is 20 psf of plan at any pitch. Multiplying it by the slope factor is a mistake, and so is dividing the dead load by it.

Lr, per foot of horizontal run (20 psf of plan) D, per foot along the slope (21.25 psf of roof surface) sloped length 19.0 ft 6 : 12 horizontal span 17 ft
Dead load follows the roof: it is spread along the 19.0 ft sloped length. Roof live load is defined on plan: it is spread along the 17 ft horizontal span. To put both on the horizontal span, only the dead load is multiplied by the slope factor.

Worked example: one rafter, five ways

The roof. A tile roof at 6 : 12, the Heavy roof preset of the Dead and Live Loads module:

ComponentLoad (psf)
Cement tile16.00
Plywood, 5/8 in2.00
Rigid insulation, 1/2 in0.75
2 × 10 framing at 16 in o.c.2.50
Total dead load D, of roof surface21.25

Tick "Include roof slope" on the roof card and enter 6 : 12. The card prints

D on the horizontal projection = 21.25 ÷ cos 26.57° = 23.76 psf

The member. A 2 × 10 Douglas Fir-Larch No. 2 rafter at 16 in o.c., horizontal span 17 ft, simple supports. Roof live load 20 psf (Table 4.3-1, ordinary pitched roofs), not reduced.

The loads on one rafter, with 16 in = 1.333 ft of tributary width:

  • Dead, on the horizontal span: 23.76 × 1.333 = 31.68 plf
  • Roof live: 20 × 1.333 = 26.67 plf
  • D + Lr: 58.34 plf

Moment and reaction:

M = 58.34 × 17² ÷ 8 = 2,108 lb-ft, R = 58.34 × 17 ÷ 2 = 496 lb

Run in the Wood & Steel Beam module (ASD, D + Lr, CD = 1.25, repetitive member factor Cr = 1.15), the bending capacity is 2,537 lb-ft and the flexure ratio is 0.83.

There are two correct ways to enter this, and they give the same result to the last digit:

Way"Sloped member"Dead load enteredMoment (lb-ft)Flexure ratio
A, correctOn, 6 : 1221.25 psf, of roof surface2,1080.83
B, correctOff23.76 psf, of plan2,1080.83
C, converted twiceOn, 6 : 1223.76 psf2,2430.88
D, conversion forgottenOff21.25 psf1,9870.78
E, rafter counted twiceOn, 6 : 1221.25 psf, and "Include member self-weight" ticked2,2440.88
  • C is on the safe side by 6%, and it is the mistake to expect once you have the plan value in hand: with "Sloped member" on, the beam module converts the dead load itself.
  • D is unsafe by 6% here. On a 12 : 12 roof the same slip leaves out 29% of the dead load.
  • E happens because the assembly already has a framing line. The 2.5 psf of rafters is in D, so the beam module's self-weight must stay off, or the framing line must come out of the assembly.

What to enter in each StructSuite module

ModuleWhat it expects
Wood & Steel Beam, "Sloped member" onSpans as horizontal runs. D per foot along the slope: the roof-surface value times the tributary width. The module multiplies D and the self-weight by the slope factor. L, Lr, S and W per foot of horizontal run, unchanged.
Wood & Steel Beam, "Sloped member" offNothing is converted. Every load is per foot of horizontal run as entered, so a roof dead load must already be the plan value.
Floor/Ceiling Joist & Rafter (span tables)The rafter span is the horizontal projection. The table is entered with a dead load of 10 or 20 psf. Neither the table text nor the AWC Span Tables for Joists and Rafters (AWC STJR), which the code refers to, states the basis of that load in words. The AWC STJR commentary gives the rafter span as L = √(8 Fb S ÷ w) (Eq. A.3.1-1), with w the total dead plus live load times the spacing and L on the horizontal projection: no pitch enters it. The table agrees: where bending governs its spans vary as 1/√(roof load + dead load): Douglas Fir-Larch #2, 2 × 8 at 16 in under the 20 psf roof live load spans 18 ft 2 in at 10 psf and 15 ft 9 in at 20 psf. So the table's dead load acts on the horizontal projection, like the roof load. Compare the plan value, D ÷ cos θ, with the column and pick the column at or above it. The optional hanger step uses the same dead load on the same span; the roof pitch entered there sets the hanger's seat and does not change the reaction.
Seismic LoadsStory weights in pounds. For a roof, D of roof surface × the roof's surface area. That is the same weight as the plan value × the plan area.
Wood-Frame Shear WallGravity loads on the wall as line or point loads. A roof's reaction comes from the member that delivers it, already on its horizontal span.
Isolated & Strip FootingThe column or wall load in force units, from the members above.

The Dead and Live Loads module does not feed the others. It is the project's load schedule, and each member module takes the numbers you carry to it.

Walls and partitions

A wall weight is per square foot of wall

The rows under FRAME PARTITIONS and FRAME WALLS, and the masonry wythes, are per square foot of wall area. A 2 × 6 stud wall with gypsum, insulation and siding is 12 psf of wall. It is not a floor load.

  • On the beam or footing under it: line load = wall psf × wall height. A 9 ft wall at 12 psf is 108 plf.
  • Exterior wall rows are complete walls. "2 × 6 @ 16 in, 5/8 in gypsum, insulated, 3/8 in siding" is the studs, the gypsum, the insulation and the siding. Adding studs or gypsum to it counts them twice.
  • Windows replace wall. "Windows, glass, frame, and sash" at 8 psf is for the glazed area. It is not added on top of a full wall.

Partitions on a floor

To carry fixed partitions as a uniform floor load, average them over the floor:

partition psf of wall × wall height × total length of partitions ÷ floor area

With 8 psf partitions 8 ft tall, 60 ft of them on a 1,200 ft² floor: 8 × 8 × 60 ÷ 1,200 = 3.2 psf of floor. Enter that as a Miscellaneous line. Ticking the 8 psf partition row into a floor or a roof assembly puts 8 psf on every square foot, two and a half times too much in this case.

Partitions that can move are live load

Where partitions may be relocated, the standard does not let you count only the ones on the plans. Section 4.3.2:

In office buildings and in other buildings where partition locations are subject to change, provisions for partition weight shall be made, whether or not partitions are shown on the plans. The partition load shall not be less than 15 psf (0.72 kN/m2) and shall not be reduced per Section 4.7.

EXCEPTION: A partition live load is not required where the minimum specified live load is 80 psf (3.83 kN/m2) or greater.

In the module this is "Include partition live load, 15 psf" in the Live loads step. A house with fixed partitions does not need it: their weight is dead load.

Live loads: reading Table 4.3-1 for a house

The Residential preset ticks eight rows. They are a list to choose from, and some exclude each other.

RowLoWhere it applies
Uninhabitable attics without storage10 psfA ceiling under an attic too low or too obstructed to store anything
Uninhabitable attics with storage20 psfA ceiling under an attic that can be used for storage
Habitable attics and sleeping areas30 psfA finished attic, and the bedrooms on any floor
All other areas except stairs40 psfLiving rooms, kitchens, halls
Ordinary flat, pitched, and curved roofs20 psfThe roof live load Lr
Stairs, one- and two-family dwellings only40 psf, and 300 lbStairs
Balconies and decks1.5 times the area served, not over 100 psfA deck off a 40 psf room is 60 psf
Handrails and guard systemsSection 4.5.1Rail loads, not a floor load
  • One attic takes one attic row. A ceiling is loaded by 10 psf or by 20 psf, not by both. Untick the rows the building does not have.
  • The 30 psf row is two places. It is the habitable attic and it is the bedroom floor. The module's building section letters it on both.
  • The roof row is Lr, not L. It goes into the roof load combinations, and it is per square foot of plan.

Three things the module does not do, so they are not assumed:

  • No live load reduction. The two "Live Load Reduction Permitted?" columns are shown as printed. The reduction of Section 4.7 and the roof reduction of Section 4.8.2 are not run. If a member qualifies and you take the reduction, enter the reduced value in that member's module.
  • No concentrated load check. The Concentrated (lb) column is the table's own. Where it can govern, such as a stair tread or a garage floor, check it in the member's design.
  • No snow. Snow load is Chapter 7 and is not part of this module.

Mistakes to avoid

  1. Putting a roof-surface dead load on a horizontal span unconverted. Multiply by the slope factor, or let the beam module do it with "Sloped member" on.
  2. Converting twice. With "Sloped member" on, enter the roof-surface value. The plan value is for a member treated as level.
  3. Converting the roof live load or the snow. They are defined on the horizontal projection.
  4. Counting the framing twice. If the assembly has a framing line, leave the member's self-weight off.
  5. Using the table's wood-joist floor rows as bare joists. They hold about 4 psf of flooring.
  6. Reading a wall weight as a floor load. Multiply by the height for a line load, or average partitions over the floor.
  7. Ticking a per-inch row without its thickness. Insulation boards, gypsum board, plywood and the concrete fills are priced by thickness.
  8. Leaving out the 10 psf of mortar under clay tile, or the 5 psf per plastered face of masonry.
  9. Trusting a preset as the whole dead load. It is the weight of its lines. Add what the project carries beyond them.
  10. Loading one ceiling with every attic row.

Frequently Asked Questions

Is roof dead load measured along the slope or on the horizontal projection?

Along the slope. The weights in ASCE 7-22 Table C3.1-1a are per square foot of the surface a material covers, so a roof assembly's total is per square foot of roof surface. To use it on a member designed on its horizontal span, multiply by the slope factor √(1 + (rise ÷ 12)²), which is the same as dividing by cos θ. At 6 : 12 the factor is 1.118.

Do I convert roof live load or snow load for the slope?

No. ASCE 7-22 Section 4.8.2 gives the roof live load per square foot of horizontal projection, and Section 7.4 says snow on a sloping surface acts on the horizontal projection of that surface. Only the dead load, which is installed on the slope, is converted.

What dead load do I enter for a rafter in the Wood & Steel Beam module?

With "Sloped member" ticked, enter the dead load of the roof surface times the tributary width, and the horizontal span. The module multiplies the dead load and the self-weight by the slope factor. With "Sloped member" off, enter the dead load on the horizontal projection, D ÷ cos θ. Both give the same result. Entering the plan value with "Sloped member" on converts it twice.

How much does the slope change the dead load?

By the slope factor: 3% at 3 : 12, 5% at 4 : 12, 12% at 6 : 12, 20% at 8 : 12 and 41% at 12 : 12. On the tile roof of the example, 21.25 psf of roof surface is 23.76 psf of plan at 6 : 12.

Are the joist values in Table C3.1-1a the weight of the joists?

No. The block is headed "Floors, wood-joist (no plaster), double wood floor". Each value is the joists and two layers of board flooring. Bare 2 × 10 joists at 16 in weigh about 2.5 psf, and the table gives 6 psf. For joists, rafters or ceiling joists alone, compute the weight from the density in Table C3.1-2 and the actual size, as the module's wood framing lines do.

Should I include the member's self-weight if the dead load already has a framing line?

No. A framing line in the assembly is the weight of the rafters or joists per square foot. Ticking the member's self-weight as well counts it twice. Use one or the other.

How do I turn a wall weight into a load on a beam?

Multiply the wall's weight per square foot of wall by its height. A 9 ft wall at 12 psf puts 108 plf on the beam under it. For partitions spread over a floor, multiply by the height and the total length and divide by the floor area.

When is the 15 psf partition live load required?

In office buildings and other buildings where partition locations are subject to change, under ASCE 7-22 Section 4.3.2, whether or not partitions are shown on the plans. It is not reduced, and it is not required where the floor live load is 80 psf or more. A house with fixed partitions carries their weight as dead load instead.

Which attic live load applies: 10, 20 or 30 psf?

One of them per attic. An uninhabitable attic without storage is 10 psf, one with storage is 20 psf, and a habitable attic is 30 psf. The 30 psf row also covers sleeping areas, so it is the bedroom floor load as well.

Does the Dead and Live Loads module reduce the live load or check concentrated loads?

No. It lists Table 4.3-1 at the tabulated values. The reductions of Sections 4.7 and 4.8.2 are not applied, and the concentrated loads are listed but not checked. Both belong to the design of the member that carries the load.